ems4.TLOG

Module for saving signal data of automation systems

The ems4.TLOG is a storage module. It is used for saving signal data of a DIGICONTROL automation system and enables long-term logging of up to 54 different signals.

  • Voltage:
    24 V DC +/- 10 %
  • Power consumption:
    Max. 3 W
  • Mounting:
    DIN rail mounting
  • Housing:
    • Housing for use in distribution boards in accordance with DIN 43880
    • Housing for use in distribution boards in accordance with DIN 43880
  • Dimensions:
    53,6 x 99,7 x 62,2 mm
  • Weight:
    120 g
  • Protection class:
    IP20
  • Operating temperature:
    +5...+45 °C
  • Ambient humidity:
    Up to 85 % rh. without condensation acc. to VDE 0160, EN 50178, Class 3K3
  • Standards / rules / guidelines / approvals:
    See EU Declaration of Conformity

  • Button:
    Front: 1x for CAN bus configuration
  • LED display:
    • CAN bus activity: (red /green) (front of device)
    • LED1 (green) USB stick has been detected
    • LED2 (yellow) data logging
    • LED3 (green) SD card has been detected
    • LED4 (red) fault, data logging not
  • System bus:
    CAN bus
  • Interfaces:
    • LIN bus
    • USB 2.0 for memory stick (Format: FAT32, max. Size: 32 GByte)
    • SD card interface (Format: FAT32, max. Size: 32 GByte)

Type
Description
ems4.HBUS-53

Mounting rail bus connector H bus 53.6