ems4.DAH3E
Digital output module with 2 x 2-stage relay outputs
with integrated LOD
DIN rail mounting
Output modules with local override combine electrical outputs with the possibility of manual intervention. They are designed for installation in a control cabinet (top hat rail). ems4.DAH3E is a module for switching up 2 x 2-stage relay outputs with an additional local override. It serves as an extension module for automation equipment of the DIGICONTROL ems series. The module’s software enables the processing of all signals in the automatic and manual mode. Furthermore, additional functions (processing of the fault signal inputs, command execution control...) are performed by the module software.
- Voltage:24 V DC +/- 10 %
- Power consumption:1 W
- Electrical connection:Via screw terminals for wires up to 1.5 mm²
- Mounting:DIN rail mounting
- Housing:Plastic housing
- Dimensions:71.6 x 109.7 x 62.6 mm
- Weight:170 g
- Protection class:IP20
- Operating temperature:+5...+45 °C
- Ambient humidity:Up to 85 % rh. without condensation acc. to VDE 0160, EN 50178, Class 3K3
- Standards / rules / guidelines / approvals:See EU Declaration of Conformity
- Inputs:
- 4x digital feedback message inputs (24 V DC)
- 2x digital fault message inputs (24 V DC)
- 2x digital inputs (24 V DC)
- Programmable command execution control
- Outputs:
- 2x 2-stage relay outputs
- Potential-free normally open contact
- Switching current 230 V AC 6 A (AC1), 2 A (AC3)
- LED display:
- 1x CAN bus activity (red/green)
- 4x LED for relay outputs (Green)
- 8x LED for digital Inputs (Red/Green parameterized)
- System bus:CAN bus
- Interfaces:CAN
Type
Description
ems4.HBUS-71
Mounting rail bus connector H bus 71.6