The DIGICONTROL ems4.CP02B - economic modular system - is a networkbased, interdisciplinary, freely programmable automation system for universal tasks in all areas of building automation for systems of all sizes. The control unit can communicate without any additional components and can be networked at an automation and management level.
- Voltage:24 V DC +/- 10 %
- Power consumption:3,8 W
- Electrical connection:Via screw terminals for wires up to 2.5 mm²
- Mounting:On vertical surfaces (wall mounting, terminals at top and bottom)
- DIN rail bus connector CAN / LIN:Max. 30 mating cycles, contact load 1 A
- Housing:Plastic housing
- Dimensions:45 x 100 x 115 mm
- Weight:250 g
- Protection class:IP20
- Operating temperature:+5...+45 °C
- Ambient humidity:Up to 85 % rh. without condensation acc. to VDE 0160, EN 50178, Class 3K3
- Standards / rules / guidelines / approvals:See EU Declaration of Conformity
- Inputs:
- 4 integrated digital inputs 24 V DC
- LED status indicator for each input
- Outputs:
- 4 integrated digital outputs 24 V DC, transistor 500 mA, short-circuit proof
- 4 integrated digital outputs 24 V DC, transistor 500 mA, short-circuit proof
- LED display:4x Status LED
- System bus:CAN bus
- Interfaces:
- 2 x RS232 / RS485 on terminals, one RS232 is modem-capable
- 1 x Ethernet 10/100 Mbit/s via RJ45 plug
- 2 x CAN interface
- 1 x LIN bus
- Integrated web server
- Can be expanded via interface modules (e.g. M-Bus, RS232 / RS485)
- IOs can be expded up to 61 ems4 modules without repeater via CAN interface
- Microprocessor system:ColdFire MCF5282
- Buffering:Lithium battery and Gold-Cap
Mounting rail bus connector ems4.TSBV5P for ems4 modules
The programming and charging cable ems4.PGU is used as connecting cable for a direct connection between the automation station (ems4.CP02B) and a notebook.
The modem cable ems4.MK10 is used as connection cable between the automation station ems4.CP02B and a modem (e.g. DC-cimo).
The modem cable ems4.MK20 is used as connection cable between the automation station ems4.CP02B and other common modems.
The control cabinet cable ems4.SK00 is used in the control cabinet as connection cable for the MultiLink (CAN bus) between the automation station (ems4.CP02B) and the terminal strip. It serves the communication with external emsX modules.
The control cabinet cable ems4.SK30 is used in the control cabinet as connection cable for the S bus (RS485) between the automation station (ems4.CP02B) and the terminal strip. It serves the communication with the automation station or the building control system.
The control cabinet cable ems4.SK40 is used in the control cabinet as connection cable for the SysLink (CAN bus) between the automation station (ems4.CP02B) and the terminal strip. It serves the integration of an automation station in a bus line.
The control cabinet cable ems4.SK50 is used in the control cabinet as connection cable for the T bus (RS485) between the automation station (ems4.CP02B) and the terminal strip. It serves the integration of an automation station in a bus line.