ems2.RTR-ECS-F
System for repairing DIGICONTROL ecs3 existing plants (front installation)
The DIGICONTROL Retrokit ems2.RTR-ECS-F enables operators of DIGICONTROL ecs3 automation systems to exchange their existing ecs3 automation stations (AS) for AS of the latest DIGICONTROL generation. This is accomplished quickly and cost-effectively, while the building is in operation. The retrokit can be used when new requirements are imposed on the automation station (e.g. Ethernet connectioin, graphical Webserver, BACnet, remote maintenance and operation) which cannot be met by an ecs3 automation station. Furthermore, the use of the retrokit in case of a defect in an existing plant with ecs3 automation station represents an economical alternative to a new construction. The original ecs3 plugs are connected to the prepared plug adapters of the retrokit. As a result, no wiring is required.
- Voltage:24 V DC +/- 15 %
- Power consumption:13 W
- Electrical connection:
- Via screw terminals for wires up to 2.5 mm²
- Ready-to-plug mounting on existing System (ecs3 terminals)
- Mounting:Front Panel mounting directly with Frame and door
- Housing:Material Plastic ABS (PA6-GF10) and macrolon
- Standards / rules / guidelines / approvals:See EU Declaration of Conformity
- Inputs:
- 21 universal inputs, freely configurable as:
- PT/NI1000, 12 bit resolution
- Digital inputs 24 V DC
- 0...10 V DC, 12 bit resolution
- 10 digital inputs 24 V DC
- Outputs:
- 8 analogue outputs 0...10 V DC, 10 bit resolution, 3 mA
- 14 digital relay outputs 230 V AC / 6 A / potential-free normally open contact
- Local override:
- 8 relay outputs: operation via sliding switch (MANUAL-OFF AUTO)
- 4 analogue outputs: operation via sliding switch (MANUAL-OFF AUTO) and potentiometer (0-100 %)
- 12 inputs for feedback of all switch positions of the local operating level
- Display:Integrated display with multifunctional keyboard for set point input, polling actual values, notifications, etc.
- LED display:
- ems2.CP14D: 24 V-LED (green), RUN-LED (green), ST-LED (red)
- ems4.KM03E: 8 x status LED for relay outputs (green), 1 x CAN bus-activity (red / green)
- ems4.DE07E: CAN bus-activity (red / green), LED 01 on printed circuit board, 10 signal LEDs on device front. LED colour configurable via software: green, red, orange
- Interfaces:
- 2 x RS232 / RS485, of which one RS232 (COM-B) is used with DCD-, DSR- and DTR signal modem operation
- 2 x CAN bus for a maximum of 1MBit/s, bus connection via slider
- 1 x LIN bus
- Ethernet interface, 10/100 MBit, RJ45 at the bottom of the housing link LED